Measures: 546 x 275 x 147 mm
EAN/GTIN: 8719076047582
The solar inverter/charger Victron Multiplus II 48/3000-35/32 230V VE.Bus Inverter Charger belongs to the Victron Multiplus II Inverter/Charger product line from Victron Energy.
The name of this inverter/charger indicates that the voltage of the inverter is 48V and the continuous power (non-linear) at 25°C is 3000VA. The AC power outlet plug is SCHUKO with an output voltage of 230 V. The battery charging current has a capacity of 35A and the capacity of the transfer switch is 32A.
| INVERTER | |
| Input voltage range | 9,5 – 17 V / 19 – 33 V / 38– 66 V |
| Output AC voltage/frequency | 230VAC ± 2% / 50Hz ± 0,1% |
| Continuous output power at 25°C (non-linear) | 3000VA |
| Continuous output power at 25 °C | 2400W |
| Peak power | 5500W |
| Max. efficiency | 95% |
| Zero load power | 11W |
| Zero load power in Search mode | 2W |
| CHARGER | |
| AC Input voltage/frequency | 187-265 V AC / 45 – 65 Hz |
| Charge voltage 'absorption' | 57,6V |
| Charge voltage 'float' | 55,2V |
| Storage mode | 52,8V |
| Battery charging current | 35A |
| Battery temperature sensor | Yes |
| GENERAL | |
| Programmable relay | Yes |
| Protection * | a-g |
| Operating temperature range | -40 to +65°C (fan assisted cooling) |
| Humidity (non-condensing) | maximum 95% |
| VE.Bus communication port | For parallel and three phase operation, remote monitoring and system integration |
| Tranfer switch | 32A |
| PowerControl and PowerAssist | Yes |
| Maximum input current | 32A |
| Auxiliary output | Yes (32A) |
| External AC sensor (optional) | 50A |
* Protection key: a) output short circuit b) overload c) battery voltage too high d) battery voltage too low e) temperature too high f) 230 V AC on inverter output g) DC ripple too high.
Standard warranty of 5 years, extendable to 10 years with an additional 10% of the initial investment. Contact us for more information.
Data sheet